Artículos 0
5114B
 
 

5114B

 

Programmable transmitter

 

  • Input for RTD, TC, mV, linear resistance, mA, and V
  • 3-port 3.75 kVAC galvanic isolation
  • Current and voltage output
  • Universal voltage supply
  • 1- and 2-channel versions
  • Loop supply > 17.1 V in Ex / I.S. zone 0
  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • The 5114 transmitter can be configured using the PReset  software and the Loop Link communications unit.

Application

  • Jumper selectable inputs for current/voltage or temperature.
  • Programmable current (0...100 mA) and voltage (0...250 VDC) inputs.
  • Linearized, electronic temperature measurement.
  • Conversion of linear resistance variation e.g, from solenoids and butterfly valves or linear movements with attached potentiometer.
  • 17.1 VDC loop and 2.5 VDC potentiometer supplies.
  • Automatic 4- / 3-wire or programmable 2-wire cable compensation.
  • Configurable sensor error detection including NAMUR NE43.

Technical characteristics

  • Active or Passive current output and selectable voltage output.
  • Separation of circuits in PELV/SELV installations.
  • I.S. barrier for temperature sensors, potentiometers, and current / voltage signals.
  • I.S. barrier with I.S. power supply for 2-wire transmitters in zone 0, 1, 2, 20, 21 and 2.

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 130 mm
Weight approx. 225 g
DIN rail type DIN 46277
Wire size 1 x 2.5 mm2 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power 2.1 W / 2.8 W (1 / 2 ch.)

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140

Response time

Temperature input, programmable (0...90%, 100...10%) 400 ms...60 s
mA / V input (programmable) 250 ms...60 s

Auxiliary supplies

2-wire supply (pin 44...42 and 54...52) 28...17.1 VDC / 0...20 mA
Programming Loop Link
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.05% of selected range
Updating time 115 ms (temperature input) 75 ms (mA / V / mV input)
Signal dynamics, input 22 bit
Signal dynamics, output 16 bit
Auxiliary voltages: Reference voltage 2.5 VDC ±0.5% / 15 mA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt100, Ni100, lin. R
Cable resistance per wire 10 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) < ±1.0°C
Sensor error current Nom. 30 μA
Sensor error detection Yes

Current input

Measurement range 0...100 mA
Min. measurement range (span) 4 mA
Input resistance: Supplied unit Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied unit RSHUNT = ∞, VDROP < 6 V

Voltage input

Measurement range 0...250 VDC -150...+150 mV
Min. measurement range (span) 5 mV
Input resistance Nom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC)
Nom. 10 MΩ (mV input)

Output specifications

Current output

Signal range 0...20 mA
Min. signal range 10 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA
Sensor error indication Programmable 0...23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA

Passive 2-wire mA output

Max. load resistance [Ω] (Vsupply-3.5)/0.023 A
Max. external 2-wire supply 29 VDC
Effect of external 2-wire supply voltage variation < 0.005% of span / V

Voltage output

Signal range 0...10 VDC
Min. signal range 500 mV
Load (@ voltage output) ≥ 500 kΩ
2-wire 4...20 mA output: Signal range 4...20 mA
Load stability, 4…20 mA output ≤ 0.01% of span / 100 Ω
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU DEMKO 99ATEX124571, II (1) GD [EEx ia] IIC
EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410
DNV-GL Marine Stand. f. Certific. No. 2.4
Su solicitud ha sido enviada con éxito - 0 Artículos en su lista
Descripción del producto Cantidad
Por favor, indique una variante ( véase ficha) - o indicar ' Variante desconocido '
Su información de contacto
Continuar navegando
No hay productos añadidos a la lista...
No tiene productos en su lista ...

Al navegar por las páginas de productos en este sitio web , tiene usted la posibilidad de añadir productos a una lista - y enviarnos su lista, solicitando con ello una oferta .
Para agregar productos a la lista , haga clic en el botón "consiga un presupuesto rápido " en las páginas de productos.

Cuando haya enviado la lista, nos pondremos en contacto con usted lo antes posible .

Si usted no presenta la lista,será visible para usted en el sitio web durante 7 días ( vamos a colocar una "cookie" en su PC o tablet ) .

Esperamos que usted encontrará la opcion útil . Por favor, vaya a las páginas de productos para agregar productos a su lista.
Gracias por su solicitud
Nos pondremos en contacto con usted por teléfono o correo electrónico tan pronto como sea posible.