Artículos 0
5420B
 
 

5420B

 

Ex power supply

 

  • 2 channels
  • 5-port 3.75 kVAC galvanic isolation
  • Output voltage > 18 V to I.S. area
  • Active current loop detection
  • Universal supply by AC or DC
  1. Overview +

  2. Technical details +


Application

  • Voltage supply with safety barrier for the supply of equipment mounted in hazardous area.
  • Voltage supply with failsafe detection of active current loop from 2-wire transmitters mounted in hazardous area.

Technical characteristics

  • PR5420B has a relay with change-over contacts available in the safe area. When the loop current is within the defined limit, the relay is ON.
  • Supply and outputs are floating and galvanically separated.

Mounting / installation

  • Mounted vertically or horizontally on a DIN rail. Up to 84 channels per meter can be mounted.

Environmental Conditions

  • Operating temperature

    -20°C to +60°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP20

Mechanical specifications

  • Dimensions (HxWxD)

    109 x 23.5 x 130 mm

  • Weight approx.

    215 g

  • DIN rail type

    DIN 46277

  • Wire size

    1 x 2.5 mm2 stranded wire

  • Screw terminal torque

    0.5 Nm

Common specifications

  • Supply

  • Supply voltage, universal

    21.6...253 VAC, 50...60 Hz or 19.2...300 VDC

  • Max. required power

    ≤ 4 W (2 channels)

  • Internal power dissipation

    ≤ 2 W (2 channels)

  • Fuse

    400 mA SB / 250 VAC

  • Isolation voltage

  • Isolation voltage, test / working

    3.75 kVAC / 250 VAC

  • PELV/SELV

    IEC 61140

  • EMC immunity influence

    < ±0.5%

  • Extended EMC immunity: NAMUR NE21, A criterion, burst

    < ±1%

Output specifications

  • Relay output

  • Max. voltage

    250 VRMS

  • Max. current

    2 ARMS

  • Max. AC power

    100 VA

  • Max. load at 24 VDC

    1 A

  • Output voltage

    > 18 VDC at 20 mA

  • Output current

    28 mA per channel (max.)

  • Relay outputs: On within limit

    > 3.8...< 20.5 mA

Observed authority requirements

  • EMC

    2014/30/EU

  • LVD

    2014/35/EU

  • EAC

    TR-CU 020/2011

Approvals

  • ATEX 2014/34/EU

    DEMKO 99ATEX126256, II (1) GD [EEx ia] IIC

  • EAC Ex TR-CU 012/2011

    RU C-DK.GB08.V.00410

Su solicitud ha sido enviada con éxito - 0 Artículos en su lista
Descripción del producto Cantidad
Por favor, indique una variante ( véase ficha) - o indicar ' Variante desconocido '
Su información de contacto
Continuar navegando
No hay productos añadidos a la lista...
No tiene productos en su lista ...

Al navegar por las páginas de productos en este sitio web , tiene usted la posibilidad de añadir productos a una lista - y enviarnos su lista, solicitando con ello una oferta .
Para agregar productos a la lista , haga clic en el botón "consiga un presupuesto rápido " en las páginas de productos.

Cuando haya enviado la lista, nos pondremos en contacto con usted lo antes posible .

Si usted no presenta la lista,será visible para usted en el sitio web durante 7 días ( vamos a colocar una "cookie" en su PC o tablet ) .

Esperamos que usted encontrará la opcion útil . Por favor, vaya a las páginas de productos para agregar productos a su lista.
Gracias por su solicitud
Nos pondremos en contacto con usted por teléfono o correo electrónico tan pronto como sea posible.