2281
 
 

2281

 

Ramp generator

 

  • Multiple functions
  • Programmable from front
  • 3-digit LED display
  • NPN and PNP inputs
  • Internal ramp time or external pulses
  • Reset or preset function
  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • The user interface consists of a 3-digit display and 3 function keys in the front to change a function, ramp time or an output signal range.

Application

  • To convert digital signals to a time-controlled analog signal with either internally entered up/down time or with external pulses for up/down function.
  • 2-phase encoder.
  • Ramp generator with internal time measurement.
  • Ramp generator with external pulses.

Technical characteristics

  • LED’s for up, reset and down.
  • 6 digital inputs make it possible to choose reset and up/down functions as either NPN or PNP input (+24 VDC).
  • Via an analog switch the up and down inputs can be switched between input filters for a pulse length > 10 ms or > 0.5 ms. The 10 ms filter is used for elimination of contact-bounce.
  • Analog standard current output of 0/4...20 mA or jumper selectable 0/2...10 mA, and standard voltages of 0/0.2...1 VDC, 0/2...10 VDC or special.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Environmental Conditions

  • Operating temperature

    -20°C to +60°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP50

Mechanical specifications

  • Dimensions (HxWxD)

    80.5 x 35.5 x 84.5 mm (D is without pins)

  • Weight approx.

    120 g

Common specifications

  • Supply

  • Supply voltage

    19.2...28.8 VDC

  • Max. required power

    2.7 W

  • Internal power dissipation

    2.4 W

  • Response time

  • Response time

    < 60 ms

  • Signal / noise ratio

    Min. 60 dB

  • Signal dynamics, output

    16 bit

  • Up ramp time

    0.1...999999 s

  • Down ramp time

    0.1...999999 s

  • External pulses

    1...15,615,744

  • Effect of supply voltage change

    < 0.005% of span / VDC

  • Temperature coefficient

    < ±0.01% of span / °C

  • Linearity error

    < 0.1% of span

  • EMC immunity influence

    < ±0.5%

Input specifications

  • Digital input

    Up / down inputs

    Reset inputs

  • NPN, digital input

    Pull up 24 VDC / 6.9 mA

  • PNP, digital input

    Pull down 0 VDC / 6.9 mA

  • Pulse length

    >10 ms / > 0.5 ms (programmable)

    > 30 ms

  • Input frequency

    50 Hz / 1 kHz (max.)

    16 Hz

Output specifications

  • Current output

  • Signal range

    0...20 mA

  • Min. signal range

    5 mA

  • Load (@ current output)

    ≤ 600 Ω

  • Load stability

    ≤ 0.01% of span / 100 Ω

  • Current limit

    20.5 mA

  • Voltage output through internal shunt

    See manual for details

  • of span

    = of the presently selected range

Observed authority requirements

  • EMC

    2014/30/EU

  • EAC

    TR-CU 020/2011

Su solicitud ha sido enviada con éxito - 0 Artículos en su lista
Descripción del producto Cantidad
Por favor, indique una variante ( véase ficha) - o indicar ' Variante desconocido '
Su información de contacto
Continuar navegando
No hay productos añadidos a la lista...
No tiene productos en su lista ...

Al navegar por las páginas de productos en este sitio web , tiene usted la posibilidad de añadir productos a una lista - y enviarnos su lista, solicitando con ello una oferta .
Para agregar productos a la lista , haga clic en el botón "consiga un presupuesto rápido " en las páginas de productos.

Cuando haya enviado la lista, nos pondremos en contacto con usted lo antes posible .

Si usted no presenta la lista,será visible para usted en el sitio web durante 7 días ( vamos a colocar una "cookie" en su PC o tablet ) .

Esperamos que usted encontrará la opcion útil . Por favor, vaya a las páginas de productos para agregar productos a su lista.
Gracias por su solicitud
Nos pondremos en contacto con usted por teléfono o correo electrónico tan pronto como sea posible.