Artículos 0
3331
 

3331

 

Temperature converter, loop-powered - isolated

 

  • Excellent accuracy, better than 0.05% of span
  • Slimline housing of 6 mm
  • Excellent EMC performance and 50/60 Hz noise suppression
  • Selectable < 30 ms / 300 ms response time
  • Pre-calibrated temperature ranges selectable via DIP-switches
  1. Overview

  2. Technical details

  3. Accessories


Application

  • The 3331 temperature converter measures a standard Pt100, TC J and K temperature sensor, and provides an isolated passive analog current output signal.
  • High 2 port isolation provides surge suppression and protects the control system from transients and noise.
  • The 3331 can be mounted in the safe area or in Zone 2 / Division 2 areas.
  • Approved for marine applications.

Technical characteristics

  • Flexibly loop powered by 5.5...35 VDC via connectors.
  • < 30 ms fast response time with simultaneous sensor error detection when selected.
  • Selectable 300 ms response time when signal dampening is needed.
  • Selectable internal/external CJC.
  • Excellent conversion accuracy in all available ranges, better than 0.05% of span.
  • Meeting the NAMUR NE21 recommendations, the 3331 provides top measurement performance in harsh EMC environments.
  • The device meets the NAMUR NE43 standard defining out of range and sensor error output values.
  • All terminals are protected against overvoltage and polarity error.
  • High galvanic isolation of 2.5 kVAC.
  • Excellent signal/noise ratio of > 60 dB.

Mounting / installation / programming

  • Selectable DIP-settings for easy configuration of more than 1000 factory calibrated measurement ranges.
  • The narrow 6 mm housing allows up to 165 units to be mounted per meter of DIN rail, without any air gap between units.
  • Wide ambient temperature range of -25...+70°C.

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13 x 2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...25 Hz ±1.6 mm
25...100 Hz ±4 g

Common specifications

Supply

Supply voltage 5.5...35 VDC
Max. required power 0.80 W
Internal power dissipation 19 mW...0.8 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Response time (0...90%, 100...10%) < 30 ms / 300 ms (selectable)
Voltage drop 5.5 VDC
Signal / noise ratio Min. 60 dB
Programming DIP-switches
Signal dynamics, input 23 bit
Signal dynamics, output 18 bit
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
Incorrect DIP-switch setting identification 3.5 mA

Input specifications

RTD input

Temperature range, Pt100 -200...+850°C
Min. measurement range (span) 10°C
Accuracy: the greater of Better than 0.05% of span or 0.1°C
Temperature coefficient: the greater of 0.02°C/°C or ≤ ±0.01%/°C
Sensor current < 150 µA
Sensor cable resistance < 50 Ω per wire
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes - selectable via DIP-switch
Broken sensor detection > 800 Ω
Shorted sensor detection < 18 Ω

TC input

Temperature range, TC J -100...+1200°C
Temperature range, TC K -180...+1372°C
Min. measurement range (span) - TC J & K 50°C
Accuracy: the greater of Better than 0.05% of span or 0.5°C
Temperature coefficient: the greater of 0.1°C/°C or ≤ ±0.01%/°C
Sensor cable resistance < 5 kΩ per wire
Cold junction compensation (CJC): Accuracy @ external Pt100 input Better than ±0.15°C
Cold junction compensation (CJC): Accuracy @ internal CJC Better than ±2.5°C
Internal CJC error detection Yes
External CJC error detection Yes - selectable via DIP-switch
Open Thermocouple detection Yes - selectable via DIP-switch

Output specifications

Common output specifications

Updating time 10 ms

Current output

Programmable signal ranges 4...20 and 20...4 mA
Load (@ current output) ≤ (Vsupply - 5.5) / 0.023 [Ω]
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 10ATEX0147 X
IECEx KEM 10.0068X
FM FM17US0004X / FM17CA0003X
DNV-GL Marine Stand. f. Certific. No. 2.4 V1-7-2
UL UL 61010-1
Su solicitud ha sido enviada con éxito - 0 Artículos en su lista
Descripción del producto Cantidad
Por favor, indique una variante ( véase ficha) - o indicar ' Variante desconocido '
Su información de contacto
Continuar navegando
No hay productos añadidos a la lista...
No tiene productos en su lista ...

Al navegar por las páginas de productos en este sitio web , tiene usted la posibilidad de añadir productos a una lista - y enviarnos su lista, solicitando con ello una oferta .
Para agregar productos a la lista , haga clic en el botón "consiga un presupuesto rápido " en las páginas de productos.

Cuando haya enviado la lista, nos pondremos en contacto con usted lo antes posible .

Si usted no presenta la lista,será visible para usted en el sitio web durante 7 días ( vamos a colocar una "cookie" en su PC o tablet ) .

Esperamos que usted encontrará la opcion útil . Por favor, vaya a las páginas de productos para agregar productos a su lista.
Gracias por su solicitud
Nos pondremos en contacto con usted por teléfono o correo electrónico tan pronto como sea posible.